Mountingandwiring
4.3 Installationonthemountingrail
Snappingontothemountingrail
TheCX51x0cansimplybesnappedontothemountingrail.Thebarclipsareinsertedonthetopsideand
undersideThensimplypositiontheblockonthemountingrailandpushitslightlyuntilitengagesonthe
righthandside.Thisisindicatedbyadistinctclick.Thebarsarethenengagedagain.Theengagementof
theindividualbarsisindicatedbyadistinctclick.TheillustrationshowstheprocedurebasedontheCX9020
asanexample.TheCX51x0has5latches(CX5120)or6latches(CX5130andCX5140)atthetopand
bottom.
Attention
Avoiddamage!
Donotforcethemoduleorapplyexcessivepressure!
Installationposition
Attention
Complywiththepermittedinstallationpositionandminimumdistances!
ThemaximumambienttemperatureforCPUmodulesmountedonaDINrailis60°C.The
orientationinwhichthedeviceisfittedmustbeselectedinsuchawaythatcoolingaircan
flowverticallythroughtheventilationholes.Theimagesshowthepermittedandtwoincor
rectinstallationpositions.Mountingmustprovideaclearanceof30mmbothaboveandbe
lowaCX51x0devicecombinationtoensureadequateventilationofthebaseCPUmodule
andthepowersupplyunit.
ThehighperformanceandthecompactdesignoftheCX51x0systemsmayresultinincreasedheat
generation.Theheatisdissipatedviaapassiveventilationsystem.Thissystemrequirestheunittobe
mountedcorrectly.Ventilationopeningsarelocatedatthetopandbottomofthehousing.Thesystem
thereforehastobeinstalledhorizontally.Thisensuresoptimumairflow.