Mountingandwiring
Theterminalsareimplementedinspringforcetechnology.Connectthecablesasfollows:
1. Openaspringloadedterminalbyslightlypushingwithascrewdriverorarodintothesquareopening
abovetheterminal.
2. Thewirecannowbeinsertedintotheroundterminalopeningwithoutanyforce.
3. Theterminalclosesautomaticallywhenthepressureisreleased,holdingthewiresecurelyand
permanently.
Wiresizewidth 0.5...2.5mm
2
AWG20..AWG14
Wirestrippinglength 8...9mm 0.33inch
LED
Ifthepowersupplyunitisconnectedcorrectlyandthepowersupplyisswitchedon,thetwoupperLEDsin
theterminalprismaregreen.TheleftLED(Us)indicatestheCPUsupply.TherightLED(Up)indicatesthe
terminalsupply.TheotherLEDsindicatetheTerminalBusstatus.AdetaileddescriptionoftheLEDscanbe
foundinsection"LEDtroubleshooting".
ULrequirements
DANGER
ComplianceoftheULrequirements
ForthecomplianceoftheULrequirementstheCXControllersshouldonlybesuppliedbya
24VDCsupplyvoltage,suppliedbyanisolatingsourceandprotectedbymeansofafuse
(inaccordancewithUL248),ratedmaximum4Amp.bya24VDCpowersource,thathasto
satisfyNECclass2.ANECclass2powersupplyshallnotbeconnectedinseriesorparal
lelwithanother(class2)powersource!ThisULrequirementsarevalidforallsupplyvolt
agesoftheCXControllers!
DANGER
ComplianceoftheULrequirements
TomeettheULrequirements,theCXControllersmustnotbeconnectedtounlimited
powersources!