Beckhoff CX1020 Manuale Utente Pagina 117

  • Scaricare
  • Aggiungi ai miei manuali
  • Stampa
  • Pagina
    / 123
  • Indice
  • SEGNALIBRI
  • Valutato. / 5. Basato su recensioni clienti
Vedere la pagina 116
Error handling and diagnostics
Embedded PC 115
CX1100-0014 power supply LEDs
Display LED Meaning
PWR power supply
The LED lights up green when the power supply is correct, but red if
there is a short circuit.
L/A off E-Bus is not connected
on E-Bus is connected / no data traffic on E-bus
blink E-Bus is connected / data traffic on E-bus
RUN Indicates the state of the EtherCAT bus:
off INIT
blink PRE-OPERATIONAL
(frequency: 200 ms on / 200 ms off)
single
flash
SAVE-OPERATIONAL
(frequency: 200 ms on / 1000ms off)
on OPERATIONAL
flickering BOOTSTRAP
(frequency: 50 ms on / 50 ms off)
double
flash
reserved for future use
(frequency: 200 ms on / 200 ms off / 200 ms on / 1000 ms off)
triple
flash
reserved for future use
(frequency: 200 ms on / 200 ms off / 200 ms on / 200 ms off / 200 ms on
/ 1000 ms off)
quadruple
flash
reserved for future use
(frequency: 200 ms on / 200 ms off / 200 ms on / 200 ms off / 200 ms on
/ 200 ms off / 200 ms on / 1000 ms off)
The functions for L/A and RUN LED are available in hardware revision > 2.0. The LEDs have no function in older
revisions.