Beckhoff CX2100­00x4 Manuale Utente Pagina 19

  • Scaricare
  • Aggiungi ai miei manuali
  • Stampa
  • Pagina
    / 45
  • Indice
  • SEGNALIBRI
  • Valutato. / 5. Basato su recensioni clienti
Vedere la pagina 18
Productoverview
ChangedsettingsarestoredfailsafeinBeckhoffdevices.
Ifthedeviceislaterexchanged,however,thesettingsthathavebeenchangedfromtheseriesstandardare
lost.TheEtherCATmastercanthenloadthechangedCoEparametersintothenewdeviceatstartup,ifitis
setupappropriately.
SothataCoEdirectoryisavailableofflineduringthepreparationforconfiguration,itcanbecontainedinthe
devicedescriptionasacopy.
TheextenttowhichtheCoEdirectoryissupporteddependsonthecapabilitiesoftheEtherCATmaster.
Tab:Online
thestatemachineoftheEtherCATcommunicationisdisplayedhere.Itcanalsobeswitchedtoadifferent
statehere.Thisisdonebyselectingthedesiredstatebyamouseclickontheappropriatebutton.The
individualstatesarebrieflydescribedbelow.Forfurtherinformation,pleaserefertotheEtherCATsystem
descriptiononourwebpage.
EtherCATStateMachine
ThestateoftheEtherCATslaveiscontrolledviatheEtherCATStateMachine(ESM).Dependinguponthe
state,differentfunctionsareaccessibleorexecutableintheEtherCATslave.Specificcommandsmustbe
sentbytheEtherCATmastertothedeviceineachstate,particularlyduringthebootupoftheslave.
Adistinctionismadebetweenthefollowingstates:
• Init
• PreOperational
• SafeOperationaland
• Operational
• Boot
TheregularstateofeachEtherCATslaveafterbootupistheOPstate.