Commissioning
systemisonlyinitiatedoncethealarmhasbeentriggered.Thisoptionshouldbeselectedinorderto
protectthebattery.Setthe“Batterytime”to2minutes,forexample.Thepermittedvaluesliebetween0
and720minutes.Thesystemwillbeshutdownoncethistimehaselapsedafterapowerfailure.This
optioncorrespondstothesameoptionthatcanbesetinthestandardUPSdialog,withthedifference
thattheshortertimesof0and1minutecanalsobeset.
SwitchoffUPS:Ifthisoptionisselected,theUPSwillswitchoffitsownoutputsaftershutdowninorder
tosavethebattery.Thisoptionalsocorrespondstothesameoptionthatcanbesetviathestandard
UPSdialog.Default:Activated!.
DelaytimeforswitchingofftheUPS[s]:Afterthisdelaythesystemshouldhaveshutdown,andthe
UPSswitchesitsoutputsoffinordertosavethebattery.Mustbesetto"0"fortheCX210009xx.
6. ClosethedialogwithOK,andthenclickApply.
ð Theconfigurationisthuscompleted.
CX210009x4 45Version1.1