I/O configuration
FM33xx 21
Linking into the Simatic Manager
The following steps are required for linking the TC-Plug into the Simatic
Manager in simple mode and for configuring it.
Install the GSD file in the Simatic Manager, add the module in the
hardware configuration and set the PROFIBUS address;
Data format: MOTOROLA; Connection Channel 0: Channel
connected; set;
n times for n channels: Add Channel compact, set the required I-
addresses for the data;
Append Channel State Open Circuit;
Append Channel State Back Voltage;
Append Measure Control;
Append Measure State;
Download the configuration into the station;
Start master;
Reset TC-Plug by switching it on and off (power is removed);